This work deals with the comparative study of different rectification methods on the performance of a 10 kW NH3-H2O absorption refrigeration machine. Three types of rectifiers, namely packed columns, tray columns and partial condensation (single) columns were studied. Numerical simulation of the mathematical model of the absorption machine shows an identical COP profile for the three types of rectifiers. Modification of a 0.43 performance absorption machine previously operating with a single rectifier resulted in 7% and 11% performance improvement for tray column and packed column rectifiers, respectively.
Author Keywords: Absorption, refrigeration machine, ammonia-water, rectifier, packed column, tray column, coefficient of performance.
Fatimata Dione1, Ababacar Thiam2, Mohamed I. S. Adjibade3, Djicknoum Diouf4, and Amadou S. Maiga5
1 LEITER, UFR-SAT, University Gaston Berger, Saint-Louis, Senegal
2 Department of physics, University Alioune Diop, Bambey, Senegal
3 Department of Mechanical engineering, Higher Polytechnic School, UCAD, Dakar, Senegal
4 LEITER, UFR-SAT, University Gaston Berger, Saint-Louis, Senegal
5 LEITER, UFR-SAT, University Gaston Berger, Saint-Louis, Senegal
Original language: English
Copyright © 2023 ISSR Journals. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Abstract
This work deals with the comparative study of different rectification methods on the performance of a 10 kW NH3-H2O absorption refrigeration machine. Three types of rectifiers, namely packed columns, tray columns and partial condensation (single) columns were studied. Numerical simulation of the mathematical model of the absorption machine shows an identical COP profile for the three types of rectifiers. Modification of a 0.43 performance absorption machine previously operating with a single rectifier resulted in 7% and 11% performance improvement for tray column and packed column rectifiers, respectively.
Author Keywords: Absorption, refrigeration machine, ammonia-water, rectifier, packed column, tray column, coefficient of performance.
How to Cite this Article
Fatimata Dione, Ababacar Thiam, Mohamed I. S. Adjibade, Djicknoum Diouf, and Amadou S. Maiga, “Comparative study of the different rectifier in an ammonia-water absorption refrigeration machine,” International Journal of Innovation and Applied Studies, vol. 39, no. 1, pp. 401–412, March 2023.